Eaton 93E UPS 100-400 kVA

Technical Specifications

General

Accessories

UPS output power rating (0.9 p.f.)

100 120 160 200 300 400 kVA

90   108 144 180 270 360 kW

External battery cabinets, internal manual bypass switch up to 120 kVA, external maintenance bypass switch, MiniSlot connectivity (Web/SNMP, ModBus/Jbus, Relay)

Efficiency in double conversion mode

(full load)

Distributed paralleling with Hot Sync technology

Inverter/rectifier topology

Audible noise

Altitude (max)

Dimensions W x D x H

 

UPS ambient service temperature

94%

4

Transformer-free IGBT with PWM

≤70dB (100-200kVA) and ≤73dB (300-400kVA) at 1 m, 75% load

1000 m without derating (max 2000 m)

600 x 800 x 1876 (mm) 100-200 kVA 1600 x 820 x 1880 (mm) 300-400 kVA

0°C to +40°C

Communications

MiniSlot

2 communication bays

Serial ports

USB, RS232

Relay inputs/outputs

Three Signal inputs

Compliance with standards

Safety (CB certified)

IEC 62040-1

EMC

IEC 62040-2, EMC Category C3

 

Input

Performance

IEC 62040-3

 

Input wiring

3 ph + neutral

Due to continuous product improvement programs, specifications are subject to change without notice.

Nominal voltage rating (configurable)

220/380, 230/400, 240/415 V 50/60 Hz

Input voltage range

+20% / -15% at 100% load +20% / -50% at 50% load

Input frequency range

42-70 Hz

Input Power Factor

0.99

Input ITHD

< 5%

Soft start capability

 

Yes

Internal backfeed protection

Yes

Battery

Battery type

100 120 160 200 300 400 kVA

90   108 144 180 270 360 kW

Charging method

94%

Battery nominal voltage (lead-acid)

4

Charging current / Model

Default

Max*

*May be limited by maximum UPS input current rating

100 120 160 200 300 400 kVA

20   20   20   20   20   20   A

40   40   80   80   120 160 A

Output

Output wiring

3 ph + neutral

Nominal voltage rating (configurable)

220/380, 230/400 (default), 240/415 V 50/60 Hz

Output UTHD

<2% (100% linear load)

Output power factor

0.9

Permitted load power factor

0.7 lagging – 0.9 leading

Overload on inverter

10 min     102-125% load

1 min       126-150% load

500 ms    >151%      load

Overload when bypass available

 

Continuous <115% load, 20 ms 1000% peak current. Note! External bypass fuses may limit the overload capability.

iEdgeSolutions